Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number NEF421025 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number NEF421025 It is listed as Circuit Breaker. component manufactured by Challenger Electrical Equipment, specifically under CAGE Code 21810. It is also accompanied by the NSN 5925009042010 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number NEF421025 with NSN 5925-00-904-2010, 5925009042010
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-904-2010 Item Description: Circuit Breaker | 5925 | 009042010 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Nef421025 | 2 | 9 | 5 |
Characteristics Data of NSN 5925-00-904-2010, 5925009042010
MRC | Criteria | Characteristic |
---|---|---|
ABTD | MOUNTING SLOT WIDTH | 0.190 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.406 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.219 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 SLOT |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES AC ALL LOCATIONS AND 25.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.062 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 5.125 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 24.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 60.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |