Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number GB2-A300A3-1-9 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number GB2-A300A3-1-9 It is listed as Circuit Breaker. component manufactured by Eaton Corp Heinemann Products Co, specifically under CAGE Code 74193. It is also accompanied by the NSN 5925004225025 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number GB2-A300A3-1-9 with NSN 5925-00-422-5025, 5925004225025
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-422-5025 Item Description: Circuit Breaker | 5925 | 004225025 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Gb2-A300a3-1-9 | 2 | 9 | 3 |
Characteristics Data of NSN 5925-00-422-5025, 5925004225025
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAT | BODY WIDTH | 4.490 INCHES MINIMUM AND 4.510 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.115 INCHES MINIMUM AND 5.135 INCHES MAXIMUM |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.256 INCHES MINIMUM AND 0.276 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.583 INCHES MINIMUM AND 4.603 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.177 INCHES MINIMUM AND 0.197 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 4.427 INCHES MINIMUM AND 4.447 INCHES MAXIMUM |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 250.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 560.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
ADAQ | BODY LENGTH | 5.990 INCHES MINIMUM AND 6.010 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT |
PKWT | UNPACKAGED UNIT WEIGHT | 4.000 POUNDS |