Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number HM2-Z11-3 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number HM2-Z11-3 It is listed as Circuit Breaker. component manufactured by Eaton Corp Heinemann Products Co, specifically under CAGE Code 74193. It is also accompanied by the NSN 5925011690995 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number HM2-Z11-3 with NSN 5925-01-169-0995, 5925011690995
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-169-0995 Item Description: Circuit Breaker | 5925 | 011690995 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Hm2-Z11-3 | 5 | 9 | 5 |
Characteristics Data of NSN 5925-01-169-0995, 5925011690995
MRC | Criteria | Characteristic |
---|---|---|
ABXD | BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
ADTV | CASE MATERIAL | METAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.625 INCHES NOMINAL |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS AND 20.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS AND 50.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE TWO |
CRTK | SWITCH TERMINAL TYPE | WIRE HOOK |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 120.0 AC AND 50.0 DC |
PKWT | UNPACKAGED UNIT WEIGHT | 3.600 OUNCES |
TTQY | TERMINAL TYPE AND QUANTITY | 4 TAB W/SCREW |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 1.562 INCHES MAXIMUM |
ADAT | BODY WIDTH | 1.250 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.875 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.925 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC ALL LOCATIONS AND 500.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.055 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.095 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | VIBRATION RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND SALT SPRAY PROOF AND FUNGUS RESISTANT AND HERMETICALLY SEALED |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 0.5 AC AND 0.5 DC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNEF |