Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number CD3-A16-U-100-115-1 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number CD3-A16-U-100-115-1 It is listed as Circuit Breaker. component manufactured by Eaton Corp Heinemann Products Co, specifically under CAGE Code 74193. It is also accompanied by the NSN 5925013303484 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number CD3-A16-U-100-115-1 with NSN 5925-01-330-3484, 5925013303484
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-330-3484 Item Description: Circuit Breaker | 5925 | 013303484 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Cd3-A16-U-100-115-1 | 5 | 9 | 5 |
Characteristics Data of NSN 5925-01-330-3484, 5925013303484
MRC | Criteria | Characteristic |
---|---|---|
ABTD | MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
ADAT | BODY WIDTH | 3.086 INCHES MINIMUM AND 3.150 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.994 INCHES MINIMUM AND 1.058 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.187 INCHES MINIMUM AND 0.251 INCHES MAXIMUM |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.718 INCHES MINIMUM AND 2.782 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
THSD | THREAD SERIES DESIGNATOR | UNC |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
AKPX | POLE QUANTITY | 3 |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 105.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 115.0 AC ALL LOCATIONS |
CMLP | THREAD QUANTITY PER INCH | 32 |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.515 INCHES MINIMUM AND 3.579 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.172 INCHES MINIMUM AND 3.296 INCHES MAXIMUM |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
ADAQ | BODY LENGTH | 5.769 INCHES MINIMUM AND 5.832 INCHES MAXIMUM |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
ADTV | CASE MATERIAL | PLASTIC |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.994 INCHES MINIMUM AND 1.058 INCHES MAXIMUM |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE AND 3 SLOT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |