Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number SCA3200WSQCC with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number SCA3200WSQCC It is listed as Circuit Breaker. component manufactured by Eaton Corporation, specifically under CAGE Code 89946. It is also accompanied by the NSN 5925008799567 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number SCA3200WSQCC with NSN 5925-00-879-9567, 5925008799567
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-879-9567 Item Description: Circuit Breaker | 5925 | 008799567 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Sca3200wsqcc | 2 | 2 | 5 |
Characteristics Data of NSN 5925-00-879-9567, 5925008799567
MRC | Criteria | Characteristic |
---|---|---|
ADAQ | BODY LENGTH | 6.562 INCHES NOMINAL |
ADAU | BODY HEIGHT | 2.594 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.250 INCHES NOMINAL |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AJEC | BOSS HEIGHT | 0.219 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 200.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRTK | SWITCH TERMINAL TYPE | WIRE LEAD |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 240.0 AC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 6.250 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.880 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 75.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 325.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 225.0 AC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |