Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number HFB31800ML with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number HFB31800ML It is listed as Circuit Breaker component manufactured by Eaton Corporation, specifically under CAGE Code 89946. It is also accompanied by the NSN 5925012622814 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number HFB31800ML with NSN 5925-01-262-2814, 5925012622814
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-262-2814 Item Description: Circuit Breaker | 5925 | 012622814 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Hfb31800ml | 5 | 2 | 3 |
Characteristics Data of NSN 5925-01-262-2814, 5925012622814
MRC | Criteria | Characteristic |
---|---|---|
AAQL | NULL | NULL |
ADAQ | BODY LENGTH | 6.000 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.062 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.187 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.500 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.125 INCHES NOMINAL |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CBME | CUBIC MEASURE | 96.000 CUBIC INCHES |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND GENERAL PURPOSE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
PKWT | UNPACKAGED UNIT WEIGHT | 14.000 POUNDS |
ADAU | BODY HEIGHT | 3.375 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
FEAT | SPECIAL FEATURES | FRONT MAGNETIC TRIP RANGE ADJUSTMENT 575.0 AMPERES MINIMUM TO 1800.0 AMPERES MAXIMUM |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |