Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number HFD3125V with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number HFD3125V It is listed as Circuit Breaker component manufactured by Eaton Corporation, specifically under CAGE Code 89946. It is also accompanied by the NSN 5925013275725 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number HFD3125V with NSN 5925-01-327-5725, 5925013275725
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-327-5725 Item Description: Circuit Breaker | 5925 | 013275725 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Hfd3125v | 5 | 1 | C | A |
Characteristics Data of NSN 5925-01-327-5725, 5925013275725
MRC | Criteria | Characteristic |
---|---|---|
AAQL | NULL | NULL |
ADAQ | BODY LENGTH | 6.000 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 5.063 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 125.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
FEAT | SPECIAL FEATURES | LINE AND LOAD TERMINALS INCLUDED |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.375 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.781 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.164 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.125 INCHES NOMINAL |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |