Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number XJL631400 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number XJL631400 It is listed as Circuit Breaker. component manufactured by Federal Pacific Electric Co Econ, specifically under CAGE Code 053Q1. It is also accompanied by the NSN 5925006154600 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number XJL631400 with NSN 5925-00-615-4600, 5925006154600
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-615-4600 Item Description: Circuit Breaker | 5925 | 006154600 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Xjl631400 | 2 | 2 | 3 |
Characteristics Data of NSN 5925-00-615-4600, 5925006154600
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
ABMK | OVERALL WIDTH | 8.250 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 200.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 500.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
ABHP | OVERALL LENGTH | 18.156 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 4.062 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 400.0 AMPERES AC ALL LOCATIONS AND 400.0 AMPERES DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 200000.0 AC ALL LOCATIONS AND 200000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +1100.0/+4000.0 AC ALL LOCATIONS AND +1100.0/+4000.0 DC ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |