Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number TEB122050WL with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number TEB122050WL It is listed as Circuit Breaker. component manufactured by General Electric Co Electric Cap, specifically under CAGE Code 60969. It is also accompanied by the NSN 5925010265114 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number TEB122050WL with NSN 5925-01-026-5114, 5925010265114
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-026-5114 Item Description: CIRCUIT BREAKER | 5925 | 010265114 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
TEB122050WL | 3 | 2 | 3 |
Characteristics Data of NSN 5925-01-026-5114, 5925010265114
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAU | BODY HEIGHT | 3.1875 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.87501 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.90625 INCHES NOMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 80.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 325.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 130.000 MAXIMUM AT 300 PCT ALL LOCATIONS AND 13.000 MINIMUM AT 400 PCT ALL LOCATIONS AND 70.000 MAXIMUM AT |
FEAT | SPECIAL FEATURES | WITH LINE AND LOAD LUGS |
SUPP | SUPPLEMENTARY FEATURES | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 DC IN ADDITION TO CPRF |
ADAQ | BODY LENGTH | 6.3125 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 2 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | RESET |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |