Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number 12L-B4 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number 12L-B4 It is listed as Circuit Breaker. component manufactured by Oakland Industries Ltd, specifically under CAGE Code 06402. It is also accompanied by the NSN 5925013797451 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number 12L-B4 with NSN 5925-01-379-7451, 5925013797451
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-379-7451 Item Description: Circuit Breaker | 5925 | 013797451 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
12l-B4 | 5 | 9 | 5 |
Characteristics Data of NSN 5925-01-379-7451, 5925013797451
MRC | Criteria | Characteristic |
---|---|---|
AJEC | BOSS HEIGHT | 0.220 INCHES MINIMUM AND 0.280 INCHES MAXIMUM |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 ALL LOCATIONS |
AKPX | POLE QUANTITY | 2 |
PKWT | UNPACKAGED UNIT WEIGHT | 2.600 OUNCES |
ADTV | CASE MATERIAL | PLASTIC |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.0 AMPERES AC AND 2.0 AMPERES DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ADAU | BODY HEIGHT | 1.770 INCHES MAXIMUM |
TTQY | TERMINAL TYPE AND QUANTITY | 4 TAB, SOLDER LUG |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ADAQ | BODY LENGTH | 2.000 INCHES NOMINAL |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT AND HUMIDITY RESISTANT |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
ADAT | BODY WIDTH | 1.540 INCHES NOMINAL |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.595 INCHES MINIMUM AND 0.655 INCHES MAXIMUM |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS AND 28.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC ALL LOCATIONS AND 2000.0 DC ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |