Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number MIL-PRF-55629-7 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number MIL-PRF-55629-7 It is listed as Circuit Breaker. component manufactured by Other Nsn, specifically under CAGE Code 81349. It is also accompanied by the NSN 5925000096667 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number MIL-PRF-55629-7 with NSN 5925-00-009-6667, 5925000096667
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-009-6667 Item Description: CIRCUIT BREAKER | 5925 | 000096667 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
MIL-PRF-55629/7 | 2 | 2 | 2 |
Characteristics Data of NSN 5925-00-009-6667, 5925000096667
MRC | Criteria | Characteristic |
---|---|---|
ADAQ | BODY LENGTH | 1.969 INCHES MINIMUM AND 2.031 INCHES MAXIMUM |
ADAT | BODY WIDTH | 0.719 INCHES MINIMUM AND 0.781 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.529 INCHES MINIMUM AND 1.591 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.099 INCHES MINIMUM AND 0.161 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 1 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 DC SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
THSD | THREAD SERIES DESIGNATOR | UNC |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/7 GOVERNMENT SPECIFICATION |
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADTV | CASE MATERIAL | PLASTIC |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.629 INCHES MINIMUM AND 1.691 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.032 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 500.0 MILLIAMPERES DC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.600 MINIMUM AT 200 PCT SINGLE LOCATION AND 8.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTI |
TTQY | TERMINAL TYPE AND QUANTITY | 2 TAB W/SCREW |