Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number MIL-C-39019-1 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number MIL-C-39019-1 It is listed as Circuit Breaker. component manufactured by Other Nsn, specifically under CAGE Code 81349. It is also accompanied by the NSN 5925010967604 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number MIL-C-39019-1 with NSN 5925-01-096-7604, 5925010967604
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-096-7604 Item Description: CIRCUIT BREAKER | 5925 | 010967604 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
MIL-C-39019/1 | 5 | 1 | C | A |
Characteristics Data of NSN 5925-01-096-7604, 5925010967604
MRC | Criteria | Characteristic |
---|---|---|
ADAQ | BODY LENGTH | 1.531 INCHES MINIMUM AND 1.562 INCHES MAXIMUM |
ADAT | BODY WIDTH | 0.594 INCHES MINIMUM AND 0.625 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.875 INCHES MINIMUM AND 0.906 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 1 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.5 AMPERES AC SINGLE LOCATION AND 2.5 AMPERES DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC SINGLE LOCATION AND 500.0 DC SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND HERMETICALLY SEALED |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-39019 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTI |
TTQY | TERMINAL TYPE AND QUANTITY | 2 WIRE HOOK |
AAQL | BODY STYLE | SINGLE POLE TYPE |
ABXD | BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
ADTV | CASE MATERIAL | METAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.669 INCHES MINIMUM AND 1.700 INCHES MAXIMUM |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION AND 50.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.500 MINIMUM AT 200 PCT SINGLE LOCATION AND 9.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
FREQ | FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
THSD | THREAD SERIES DESIGNATOR | UNEF |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-39019/1 GOVERNMENT SPECIFICATION |