Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number Q330 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number Q330 It is listed as Circuit Breaker. component manufactured by Siemensallis Inc, specifically under CAGE Code 60555. It is also accompanied by the NSN 5925001245015 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number Q330 with NSN 5925-00-124-5015, 5925001245015
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-124-5015 Item Description: Circuit Breaker | 5925 | 001245015 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Q330 | 2 | 9 | 5 |
Characteristics Data of NSN 5925-00-124-5015, 5925001245015
MRC | Criteria | Characteristic |
---|---|---|
AAQL | NULL | NULL |
ADAQ | BODY LENGTH | 2.875 INCHES NOMINAL |
ADAT | BODY WIDTH | 3.000 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
APNQ | ARC QUENCHING METHOD | AIR |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
ADAU | BODY HEIGHT | 2.375 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.187 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 TERMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 3 CLIP AND 3 COMPRESSION |