Using the Request for Quote (RFQ) form provided on this page, you can request competitive procurement options on part number 129-203-101 with rapid responses always offered by our staff. To ensure that you locate and procure exactly what you need with ease, we list parts with as much information as we can. For example, part number 129-203-101 It is listed as Circuit Breaker. component manufactured by Wood Electric Operations Potter And Brumfield, specifically under CAGE Code 79405. It is also accompanied by the NSN 5925003062826 for ease of organization, the first digits of the NSN indicating that the part belongs to FSC 5925 Circuit Breakers.
NSN Information for Part Number 129-203-101 with NSN 5925-00-306-2826, 5925003062826
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-306-2826 Item Description: Circuit Breaker | 5925 | 003062826 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
129-203-101 | 5 | 1 | C | A |
Characteristics Data of NSN 5925-00-306-2826, 5925003062826
MRC | Criteria | Characteristic |
---|---|---|
AAJE | THREAD PITCH DIAMETERS | +0.1177/+0.1214 INCHES |
ADAQ | BODY LENGTH | 2.510 INCHES MAXIMUM |
ADAT | BODY WIDTH | 0.730 INCHES MINIMUM AND 0.780 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.660 INCHES MINIMUM AND 1.960 INCHES MAXIMUM |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.800 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 3.0 AMPERES AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.135 MINIMUM AT 200 PCT SINGLE LOCATION AND 1.850 MAXIMUM AT 200 PCT SINGLE LOCATION |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 2.0 DC |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTI |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADTV | CASE MATERIAL | PLASTIC |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.046 INCHES MINIMUM AND 2.078 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.109 INCHES MINIMUM AND 0.171 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 1 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
THSD | THREAD SERIES DESIGNATOR | UNC |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/2 GOVERNMENT SPECIFICATION |